AL71 Secondary Return Sensor (RRS)

Cause
  • Secondary Return Sensor (RRS) is out of range.
Components Troubleshooting Corrective actions
Secondary Return Sensor (RRS) Perform Pre-trip P5: If P5 passes, no further
action is required.


If P5 fails, replace the defective sensor as determined by P5, refer to TEMPERATURE SENSOR Service Section 6.24.