730 |
RH sensor missing |
Description |
RH sensor communication missing |
Cause |
Indication of defective RH sensor, or lack of or improper connection |
Trouble
shooting |
Possible causes:
- Communication with RH sensor broken.
- Defective RH sensor.
- X10 cable is defective.
- Main controller defective.
- CO2 sensor defective (for some models).
- O2 sensor defective (for some models).
Accompanied alarms:
- AL 302 or one or more AL 9XX may also be active. Trouble shooting: Verify that cable RH-com is mounted correctly (and is not damaged) according to wiring diagram inside the controller cabinet.
- Verify that plugs are properly connected.
- Verify that there are correct voltages 12 V DC between 1 and 4 on X10 or between 1 and 2 on X73.
- If model has CO2 and or O2 sensor, see troubleshooting for AL 740 and or AL 760 in “Operating and service manual Controlled Atmosphere”
- Measure with a multimeter that there is a small DC signal between 2 and 3 on X10, and between 2 and 3 on X75.
a) If there is no signal: The main controller is defective and must be replaced. b) If there is signal: The RH sensor is defective and must be replaced. |
Criteria |
Communication with RH sensor not possible |