07 R-134 Compressor Current Too Low (Check Alarm)

Thermo King Alarm Code
Description Corrective Action
Compressor Current Too Low (Check Alarm)
  • Occurs during Pretrip (PTI) or Function test only.
  • Compressor power consumption is 25% below expected current draw (below approximately 9 amps).
  • Indicates:
  • Defective or open fuse CB 7A, high pressure cutout switch or connection in plug j19 between pins 7 & 8
  • No signal on plug J11 on pin 8
  • Defective compressor relay
  • Defective volt or amp meter on relay board
  • Low refrigerant charge
  • Defective compressor or valve plate
  • Enter Manual Function Test menu. Start and  check current draw of the following components separately and together: compressor, compressor 25%, condenser fan and evaporator fan (high and low). If relay does NOT energize and the LED above the compressor relay is NOT ON, check for a defective cable No.2, main relay board or controller.
  • Check discharge and suction pressure gauge readings. Evaluate readings based on current cargo and ambient temperatures.
  • Check volt and ampere meter.
  • Check power supply volts.

NOTE: *If both alarms 06 and 07 are activated, the alarms are caused by a large difference in measured amps. Enter Function Test and start condenser fan, compressor, compressor 100% and evaporator fans on HIGH speed. Check the amps measurements. if necessary, check the resistance of the motor windings.