102 | Tret invalid |
---|---|
Description | Return Air Temperature Sensor Invalid |
Cause | Indication of defective return air temperature sensor or its measuring circuitry |
Trouble shooting |
Possible causes:
Trouble shooting:
a) If the resistance is out of range, see “30.2 Temperature Sensor [°C] - Resistance Table” p. 185, the temperature sensor and cable are defective and should be replaced. b) If the resistance is within range, perform main controller check “16.1 Trouble shooting for Star Cool main controller” p. 60 before replacing main controller. |
Criteria | Sensor is defective and the missing sensor reading has been substituted by a value from AAS system. See “6.18 Alarm Action System (AAS)” p. 19 |
102 StarCool Alarm Codes And Actions