203 | Pdis invalid |
---|---|
Description | Compressor Discharge Pressure Transmitter Invalid |
Cause | Indication of defective compressor discharge pressure transmitter or its measuring circuitry |
Trouble shooting |
Possible causes:
Trouble shooting: Compare pressure in display with service gauge. Disconnect the cable for Pdis from the main controller according to the wiring schematics inside the control cabinet and from the HP transmitter.
Figure for AKS Figure for NSK 3.Check the cable (measure the resistance in the cable). If the cable is defective, replace cable. 4. Mount the cable for Pdis in controller cabinet and on the transmitter. Disconnect signal wire on main controller. Measure voltage between wire and GND on main controller. AKS: If voltage is below 0.5 V DC, transmitter or connection between transmitter and cable is defective. If voltage is between 0.5 V DC and 4.5 V DC, continue to 5). NSK: If voltage is below 0.37 V DC, transmitter or connection between transmitter and cable is defective. If voltage is between 0.37 V DC and 4.0 V DC, continue to 5). 5. Mount signal wire. Measure voltage between SIGNAL and GND. AKS: If voltage is between 0.5 V DC and 4.5 V DC and this alarm is still active, replace main controller. NSK: If the voltage is between 0.37 V DC and 4.0 V DC and this alarm is still active, replace main controller. 6. Before replacing main controller see “16.1 Trouble shooting for Star Cool main controller” p. 60 |
Criteria | Value below alarm limit 0.1 BarE (2 Psi) or above 30/31.9 BarE (435/462 Psi). Value invalid for 30 sec. for alarm activation. |
203 StarCool Alarm Codes And Actions
Engineering Workshop - Pura Kencana, Seri Gading, Batu Pahat, Johor
0187652032 (WhatsApp only)
Subscribe to:
Posts
(
Atom
)