Trouble
shooting |
Possible causes:
- Defective Tevap temperature sensor.
- Defective Psuc pressure transmitter.
- Defective heaters.
- Defective hot gas valve.
- Evaporator was fi lled with too much ice.
Accompanied alarms:
Trouble shooting:
- Defrosting is terminated when Tevap rises above +15°C (+59°F). Check Tevap and Psuc sensors according to trouble shooting in alarms AL 123 and AL 207.
- The heaters may be defective. Start the heaters in manual mode and see if the current consumption is higher than 5 A per phase else the heaters or the power cables for the heaters may be defective.
- The hot gas valve is not working properly and the heaters may be defective. Check trouble shooting for the hot gas valve in alarm AL 844.
- See if the evaporator is fi lled with ice (through the inspection holes). Be careful with the evaporators fans!
|