P8 Tests - Perishable Mode Tests: Pre-trip tests P7-0 and P7-1 must have passed or have been skipped for these tests to execute.
P8-0 Perishable Mode Test |
If the control temperature is below 15.6 C., the setpoint is changed to 15.6 C., and a 180 Minute timer is started. The control will then be placed in the equivalent of normal heating. If the control temperature is above 15.6 C. at the start of the test, then the test proceeds immediately to test 8-1. While in test 8-0 the right display will show the value of the control temperature.” The test fails if the 180 Minute timer expires before the control temperature reaches setpoint - 0.3 C. If the test fails, it will not auto-repeat. There is no pass display for this test. Once the control temperature reaches setpoint, the test proceeds to test 8-1. |