17 Condenser Fan Current Too Low (Check Alarm)

Thermo King Alarm Code
Description Corrective Action
Condenser Fan Current Too Low (Check Alarm)
  • Occurs during Pretrip (PTI) or Function test only.
  • Condenser fan power consumption is 25% below expected current draw (below 0.5 to 0.7 amps, depending on voltage).
  • Indicates:
  • Defective condenser fan motor relay
  • Defective or open fan motor internal over temperature protection switch
  • Defective volt or amp meter on relay board.
  • Enter Manual Function Test and start condenser fan. Make sure the fan starts. Check fan motor volts and amps.
  • Check power supply volts and amps.
  • Check volt and ampere meter.