00 Supply Air Sensor Open Circuit (Check Alarm)

Thermo King Alarm Code
Description Corrective Action
Supply Air Sensor Open Circuit (Check Alarm)
  • Sensor circuit resistance higher than 100,000 ohms.
  • Temperature below -70C (-94F)
  • Indicates:
  • Open circuit to left or right hand sensor
  • Defective or wrong sensor
  • Defective relay board
  • Defective cable No. 1 or cable No. 3
  • Defective controller
  • Identify defective sensor (left hand or right hand) by viewing Data menu.
  • Check sensor resistance between pins 1 and 2 on plug J15 and between pins 7 and 8 on plug J14. Resistance must be 2,000 ohms at 25C (77F).
  • Check cable No.1 and cable No.3 between the controller and relay board.
  • Check evaporator air flow.