Supply Air Sensor Open Circuit (Check Alarm)
- Sensor circuit resistance higher than 100,000 ohms.
- Temperature below -70C (-94F)
- Indicates:
- Open circuit to left or right hand sensor
- Defective or wrong sensor
- Defective relay board
- Defective cable No. 1 or cable No. 3
- Defective controller
|
- Identify defective sensor (left hand or right hand) by viewing Data menu.
- Check sensor resistance between pins 1 and 2 on plug J15 and between pins 7 and 8 on plug J14. Resistance must be 2,000 ohms at 25C (77F).
- Check cable No.1 and cable No.3 between the controller and relay board.
- Check evaporator air flow.
|