58 Phase Sensor Error MP4000
Description
Phase Sensor Error
- Occurs during pretrip (PTI) or function test only.
- During Phase Sensor Test, while direction is
reversed, the condenser fan and compressor is
tested.
- If the current consumption of the condenser fan
is below 0,5A on each phase.
- If the current consumption of the compressor is
below 2,0A on each phase.
- Indicates:
- Defective phase relay.
- Defective power module.
Corrective Action
- Start a Manual Function Test. With reverse
phase direction selected, check the condenser
fan runs reversed direction and the
compressor is activated and makes loud
noise. Allow only for short time activation max.
5 sec.