801 | Controller |
---|---|
Description | Controller Internal Voltage Reference Fault |
Cause | - |
Trouble shooting |
Possible causes:
B. Measure voltage for all sensors. Should be between 4.80V DC and 5.20V DC for temperature and pressure transmitters. Humidity sensor must be between 12.00V DC and 34.00V DC. If not ok, the sensor or cable is defective. Replace sensor. C. Measure outlet on transformer between T3 and T4. Correct range 15.30V AC – 24.30V AC. Measure between T5 and T6. Correct range 18.86V AC – 30.00V AC. If within range transformer is ok. D. Replace main controller. |
Criteria | One or more of the internal reference voltages are out of limits |
801 StarCool Alarm Codes And Actions