Description |
---|
Alarm 35 is triggered by the voltage output being out of range (less than 0.95v or greater than 5.05v) for 30 minutes, or ten unsuccessful automatic calibration attempts. This alarm will remain active until the sensor is in-range or a successful carbon dioxide (CO2) zero calibration is performed. |
Carrier CA Alarm Codes AL35