Cd30 In-Range Tolerance

The in-range tolerance will determine the temperature band around the set point which will be designated as in-range. For normal temperature control, control temperature is considered in range if it is within setpoint in-range Tolerance. There are four possible values:

1 = +/- 0.5 C (+/-0.9 F)
2 = +/- 1.0 C (+/-1.8 F)
3 = +/- 1.5 C (+/-2.7 F)
4 = +/- 2.0 C (+/-3.6 F) - Factory Default


If the control temperature is in-range, the green IN-RANGE light will be illuminated. In-range tolerance shall be set to +/- 2.0 C upon activation of dehumidification or bulb mode (Cd33, Cd35, Cd48). When CCPC is actively controlling, in-range tolerance is not considered. “-----“ will be displayed whenever Dehumidification or Bulb mode is enabled or when CCPC with six hour re-activation is actively controlling. “-----“ will be displayed whenever Frozen Economy Mode is operating.