Cd53 Automatic Set point Change Mode Parameter Selection

ASC-mode:
Cd53 increments of (1 day)_(1hr), Display: default “0_0 “
“done” mm-dd this will be display is ASC has completed
“ASC” value “On” “OFF” Display /Select: default “OFF“
“nSC” value “1 - 6“ (This is the value “n” for the subsequent entries).
“SP (n-1)” value C / F on 0.1 degree increments Display/Select: default
“10.0 C“
“DAY (n-1)” value “1 – 99” increments of 1 Display/Select: default “1“
“SP (n)” value C / F on 0.1 degree increments Display/Select: default “10.0 C
Initially Cd53 will display current count down timer increments of (1 day)_(1hr),
default “0_0
Pressing ENTER key will take the interface down into a hierarchy of parameter
selection menus, (mode, act, treat, days, probe and spnew setting). Pressing
ENTER key in any of the parameter selection menus selects the currently displayed
parameter and causes the interface to descend into the next parameter
selection menu. All parameter selection menus alternate between a blank display
and the current selection in the right hand display.
Pressing CODE SELECT key in a selection menu cancels the current selection
activity and ascends back up to the next higher selection menu (or to Cd53 display
mode if that is the next higher).
If the operator does not press any key for five seconds the interface reverts to
normal system display and the current selection menu is cancelled, but any previously
committed changes are retained.
Available parameters and parameter ranges are a function of configuration options
and previously selected parameters as indicated above.
Parameter with the exception of “ASC” may not be altered if Cd53 is re-entered if
“ASC” is “On”. When ASC has completed including reaching the last setpoint
“done” on the left display and the MONTH DAY of completion on the right display
will be displayed as the second entry in the menu. Turning ASC off clears this
entry. This action also resets Cd53 to initial time remaining. ASC must then be
turned on to view or modify the additional parameters.
Whenever any auto pretrip test or Trip Start is initiated, ASC mode goes to OFF.