| Alarm Logic |
E207 Defrost can not be completed within 100 minutes |
| Possible Causes |
Malfunction
|
| Trouble Shooting |
If defrost does not complete, there may be low hot-gas temperature, Insufficient hot-gas circulation Check sensors (EOS, RS, HPT, LPT, DCHS) and valves (HSV, ISV), replace as needed (refer to alarm diagnosis 018 019 020) |
| Controller Action |
E207 Alarm display only |
Daikin E207