Alarm
Logic |
E103 Compressor operating current is high (Electronic type OC)
E105 Compressor operating current is high (Micro computer type OC) |
Possible
Causes |
E103
Single phase operation due to faulty contact
- Compressor magnetic contactor / Compressor wires / Compressor terminal
- Compressor locked / Compressor thermal protector CTP activated Faulty / PT/CT board
(EC5) / Faulty controller (CPU and I/O board)
- Wrong initial set up of PT/CT board (Jumper wire)(Single or Dual power supply, 10HP or 5HP)
E105
Single phase operation due to faulty contact
- Compressor magnetic contactor / Compressor wires / Compressor terminal
- Compressor locked / Faulty PT/CT board / CPU board failure
- Incorrect initial setting of controller (Single or Dual power supply, 10HP or 5HP)
|
Trouble
Shooting |
If PT/CT board is replaced.
- Check power setting Single or Dual
- Check horsepower setting 10HP or 5HP (refer to jumper check table)
Remove possible cause (listed below) of overload or starting error of the compressor.
- High differential pressure when unit is starting up / Liquid refrigerant / Excessive oil / Overcharge refrigerant / Compressor motor coil failure / Compressor motor shaft failure
|
Controller
Action |
E103 Restart after 3 minutes (continuous restart)
E105 Restart after 3 minutes (continuous restart) |