Alarm Logic |
E107
|
|
Possible Causes |
Refrigeration system restriction : Drier / Filter
|
|
Trouble Shooting |
Discharge gas temperature is abnormal 1. Check mounting position of discharge gas temperature sensor |
Replace the sensor if resistance value is not with specification. |
2. Liquid line Check drier and filter for restriction. Replace parts if needed |
Replace as needed if it is restricted | |
3. Check drier for restriction and ISV outlet line strainer. Replace parts if needed | ISV is open when DCHS temperature is high. Repair as needed if ISV does not open. Replace the parts as needed | |
4. EV opening error Check EV coil and body with alarm diagnosis 002 EV check (refer to page 5-4) | ISV is open when DCHS temperature is high. Repair as needed if ISV does not open. Replace the parts as needed | |
5. Refrigerant level Unit might be low on refrigerant. Make sure there are no leaks and then charge system with specified amount. | ||
Controller Action |
E107 [If discharge gas temperature is abnormal] Restart after 3 minutes. 9 restart attempts. Retry after 4 hours. If unit can't operate after 9 attempts, Retry after 4 hours repeatedly. [If EV opening error continues 5 minutes] Restart after 3 minutes. F803 alarm occur when E107 is generated two times. Unit stopped. |