Daikin E203

Alarm
Logic
E203
  • If supply sensor is 3°C lower than set point for 3 minutes in chilled mode
  • If supply sensor is 0.5°C lower than set point for 30 minutes in chilled mode
Possible
Causes
  • Cooling load is reduced rapidly
  • Faulty low pressure transducer (LPT)
  • Faulty discharge gas temperature sensor (DCHS)
  • Faulty suction modulation valve (SMV)
  • Faulty discharge gas bypass solenoid valve (BSV)
  • Fuse circuit disconnected (Fuse 2)
  • Evaporator fan motor abnormality
Trouble
Shooting

  • Replace LPT if pressure difference between pressure gauge and sensor reading is greater than 30kPa
  • Check installation of DCHS
  • Reset SMV opening if SMV opening is fixed at around 79pLs (24%)
  • Check wiring and connector CN12 on I/O board for BSV if SMV opening is except 79pls

  • Replace Fuse Fu2 if it is open
  • Check evaporator fan motor magnetic contacts bave failed
  • Check SMV wiring and connector CN9 on I/O board
Controller
Action
E203 Restart after 3 minutes