Alarm Logic |
E203
- If supply sensor is 3°C lower than set point for 3 minutes in chilled mode
- If supply sensor is 0.5°C lower than set point for 30 minutes in chilled mode
|
Possible Causes |
- Cooling load is reduced rapidly
- Faulty low pressure transducer (LPT)
- Faulty discharge gas temperature sensor (DCHS)
- Faulty suction modulation valve (SMV)
- Faulty discharge gas bypass solenoid valve (BSV)
- Fuse circuit disconnected (Fuse 2)
- Evaporator fan motor abnormality
|
Trouble Shooting |
- Replace LPT if pressure difference between pressure gauge and sensor reading is greater than 30kPa
- Check installation of DCHS
- Reset SMV opening if SMV opening is fixed at around 79pLs (24%)
- Check wiring and connector CN12 on I/O board for BSV if SMV opening is except 79pls
- Replace Fuse Fu2 if it is open
- Check evaporator fan motor magnetic contacts bave failed
- Check SMV wiring and connector CN9 on I/O board
|
Controller Action |
E203 Restart after 3 minutes |