Alarm Logic |
E401 Supply air sensor (SS) is not functioning correctly E402 Supply air sensor for Data-recorder (DSS) is not functioning correctly E403 Return air sensor (RS) is not functioning correctly E404 Return air sensor for Data-recorder (DRS optional) is not functioning correctly |
|
Possible Causes |
Device malfunction Sensor failure / Controller failure / Broken wire / Connector disconnected / short circuit |
|
Trouble Shooting |
1. Check connector CN43 and make sure it is properly installed |
1. Proceed to the next step if the alarm still occurs |
2. Remove CN43 connector and check sensor resistance |
2. Sensor is functioning if it matches the resistance and temperature sensor characteristics table (refer to page 6-2 Check CPU board) | |
Controller Action |
E401 Abnormal SS ~ 1st 1st backup by DSS ~ 2nd 2nd backup by RS–2°C E402 Abnormal DSS ~ backup by SS E403 Abnormal RS ~ 1st backup by DRS (optional) ~ 2nd backup by SS+5°C E404 Abnormal DRS (optional) ~ backup by RS |
Daikin E401 (SS)~E402 (DSS)~E403 (RS)~E404 (DRS-optional)