Alarm Logic |
E413 Low pressure transducer (LPT) is not functioning correctly E415 High pressure transducer (HPT) is not functioning correctly |
|
Possible Causes |
Device malfunction
|
|
Trouble Shooting |
1. Check connector CN44 and make sure it is properly installed | 1. Proceed to the next step if the alarm still occurs |
1-1. Connect gauge manifold, compare the value of pressure gauge and HPT 1-2. Connect gauge manifold, compare the value of pressure gauge and LPT LPT or HPT value shows by monitoring data or display mode sensor. (refer to page 2-12) |
1-1. Replace HPT if the difference is greater than 100kPa 1-2. Replace LPT if the difference is greater than 30kPa |
|
2. Remove connector CN44 on CPU board and check if there is 5VDC from the controller LPT : CN44 No.1-2-3 (Black-White-Red) HPT : CN44 No.4-5-6 (Black-White-Red) Black-Red : 5VDC CPU board CN44 |
2. If the input to transducer is 5VDC, check the transducer If input is less than 5V, check controller and wiring | |
Controller Action |
E413 Backup operation E415 Backup operation |