Daikin F701

Alarm
Logic
F701 Main power supply voltage error
  • Main power is greater than 535V or less than 300V when start within 2 seconds
  • If phase (in-phase or reverse-phase) is unknown
  • If main power frequency is greater than or equal to 70Hz, or less than equal to 40Hz
Possible
Causes
  • Main power is greater than 535V or less than 300V
  • Faulty voltage detection : Connector disconnected / Faulty PT on PT/CT board (other than disconnection and short circuit) / S phase is open
  • Main power frequency is greater than or equal to 70Hz, or less than equal to 40Hz
Trouble
Shooting
1. Main power check
  • Check if the main power supply remains in allowable range (300V-535V)
1. Supply power is in range
  • Damage to parts may accrue

2-1. R,S,T phase missing check
  • Check if there is a missing phase on the power side of circuit breaker
2-2. Check if there is a broken wire (open) on the secondary side of circuit breaker
  • Between C/B and CN2 (PT/CT board)
  • Between C/B and Tr1 and CN1 (I/O board)
2-1. Replace or repair if there is problem in power plug or cable
2-2. If a phase is missing repair as
needed Repair if there is a broken wire
(open) on the secondary side of circuit breaker
Controller
Action
F701 Unit stopped