Alarm Logic |
F705 S phase is open |
Possible Causes |
Power supply voltage abnormal : S phase is open / Main power supply is faulty Faulty power supply equipment : Faulty power plug contacts / Power cable contact faulty / Faulty PT/CT board |
Trouble Shooting |
1. Check if there is phase missing on power supply equipment side | 1. Provide correct power supply if there is a power phase missing. |
2. Check if there is a broken wire (open) in power plug or power cable on the power side of circuit breaker | 2. Repair as needed. | |
3. Check for broken wire (open) on the secondary side of circuit breaker
|
3. Repair as needed |
Controller Action |
F705 Unit stopped |