Alarm Logic |
E707 Main power supply voltage out of range |
Possible Causes |
Supply power is abnormal, unit stopped during operation If main power is greater than 535V for 15 seconds or less than 334V during operation |
Trouble Shooting |
Repair main power supply Once the unit is stopped, restarts after 3 minutes 9 attempts. If voltage is within specification unit will run |
Controller Action |
E707 Restart after 3 minutes. 9 restart attempts. Retry after 4 hours |