Mitsubishi Alarm Code #206 cause 3



Alarm Code #206
Model CPE52, 53, 14, 15, 15V, 16
Failure Forced defrost termination failure
Countermeasure
<< Cause –(3) >>
Defective Heater relay and Heater conductivity failure
< Check > ( Refer to Page F-10, 13, 19 )
Apply electric current to the heater under the test mode, and check
if HK2 ( and / or HK3 ) thermostat ( Heater overload protector ) does not work and
HR1( and / or HR2 ) relay operates and check the current.
And also check the current value displayed on the personal computer, the LED or the LCD.
The standard current value * is shown on Instruction Manual for each Reefer unit.
* Standard current value ( A ) ( at AC 400V ) of CPE16-2BA3E2V
HR1 L1( 15B ) / L2( 24B ) / L3( 20B ) : 3.7( A ) / 7.4( A ) / 3.7( A )
HR2 L1( 15A ) / L3( 20A ) : 3.7( A ) / 3.7( A )
< Action >
Retighten the cause.



No comments :