Mitsubishi Alarm Code #323, #325, #327, #329 cause 3



Alarm Code #323, #325, #327, #329 ( Optional Code )
Model CPE52, 53, 14, 15, 15V, 16
Failure Short circuit of Cold treatment sensor ( TCT1, TCT2, TCT3, TCT4 )
Countermeasure
<< Cause -(3) >>
Defective sensor ( TCT1, TCT2, TCT3 or TCT4 )
< Check > ( Refer to Page F-21 )
Check the sensors are out of –45 to 70°C range with the personal computer display or the LCD.
Then remove the sensors from the terminal block TB11 or TB12, and check the resistance
between VRF – 63, VRG – 66, VRF – 67, or VRF – 61.
< Action >
• Out of approx. 1 - 120 kohm range : Replace TCT1, TCT2, TCT3, or TCT4.
• In case only the temperature displayed on the personal computer deviates,
adjust the offset data ( Refer to Instruction Manual of Hand – held computer ).

No comments :