Alarm Code #330
Model CPE52, 53, 14, 15, 15V, 16
Failure High refrigerant pressure sensor ( HPT
) failure
Countermeasure
<< Cause -(3) >>
Defective High refrigerant pressure sensor ( HPT )
< Check > ( Refer to Page F-18 )
Compare the sensor DC output voltage between 1(RED) and 2(WH) of
CN24
and the pressure value ( the personal computer display, the LED,
the LCD or a pressure gauge indication ).
<< Relation between the output voltage and the pressure
>>
< CPE52, 14, 16 >
Sensor DC output voltage (V) = { 0.001165 × Pressure (kPa) + 1 } ± 0.08
< CPE53, 15, 15V >
Sensor DC output voltage (V) = { 0.001632 × Pressure (kPa) + 1 } ± 0.08
< Action >
• Out of Range : Replace HPT.
• In case the pressure value display on the personal computer, the
LED or the LCD deviates,
adjust the offset data ( Refer to
Instruction Manual of Hand – held computer ).