Mitsubishi Alarm Code #331 cause 3



Alarm Code #331
Model CPE52, 53, 14, 15, 15V, 16
Failure Low refrigerant pressure sensor ( LPT ) failure
Countermeasure
<< Cause -(3) >>
Defective Low refrigerant pressure sensor ( LPT )
< Check > ( Refer to Page F-18 )
Compare the sensor DC output voltage between 1(GRN) and 2(YEL) of CN23
and the pressure value ( the personal computer display, the LED, the LCD or a pressure gauge indication ).
<< Relation between the output voltage and the pressure >>
< CPE52, 14, 16 >
Sensor DC output voltage (V) = { 0.00204 × Pressure (kPa) + 1 } ± 0.08
< CPE53, 15, 15V >
Sensor DC output voltage (V) = { 0.004079 × Pressure (kPa) + 1 } ± 0.08
< Action >
• Out of Range : Replace LPT.
• In case the pressure value displayed on the personal computer, the LED or the LCD deviates,
adjust the offset data ( Refer to Instruction Manual of Hand – held computer ).