Mitsubishi Alarm Code #332 cause 2



Alarm Code #332
Model CPE52, 53, 14, 15, 15V, 16
Failure Detected pressure shift failure of High or Low refrigerant pressure sensor ( HPT or LPT )
Countermeasure
<< Cause –(2) >>
Opening failure of Modulating valve ( MV )
< Check > ( Refer to Page F-17 )
Check if vibration noises are head at an interval of approx. 1 – 2 sec
when MV is opened and closed under the test mode.
(i) In case no noise is heard :
Disconnect the connector CN21 and check the resistance between 1(YEL) – 2(BLU) Pin,
and 3(BLK) – 4(WH) Pin.
(ii) In case no noise is heard :
Check LPT – OFF with “ the Classification Society test ” under the test mode and cancel
immediately the test by pressing ENTER key.
Next, Open MV with “ the MV test ” under the test mode and check if the pressure rises or not.
< Action >
(i) Out of approx. 100 – 160 ohm range : Replace MV.
(ii) In case the low pressure does not rise : Replace MV.