Mitsubishi Alarm Code #332 cause 3



Alarm Code #332
Model CPE52, 53, 14, 15, 15V, 16
Failure Detected pressure shift failure of High or Low refrigerant pressure sensor ( HPT or LPT )
Countermeasure
<< Cause –(3) >>
• Poor contact of the connector CN10, CN23 and CN24
• Poor contact of terminals on the terminal block TB11
• Defective LPT • Defective HPT
• Defective PCB – C board
< Check >
• Open fully (100%) MV and EEV for more than 5min under the test mode to take the balance of
pressure in the refrigerant system.
Check if the relative pressure difference between the high pressure and the low pressure
is larger than approx. 980kPa ( 1kgf / cm² ) with the personal computer display, the LED, the LCD
or a pressure gauge. And then loosen and tighten again the flares of HPT
and LPT, and observe if there is any change.
• Perform the same check as described on the #330 and #331. ( Refer to Page 90 – 101 )
< Action >
Perform the same action described on the #330 and #331. ( Refer to Page 90 – 101 )