Mitsubishi Alarm Code #335, #336 cause 2



Alarm Code #335, #336
Model CPE15 ( Only Two Compressor type )
Failure Disconnection (#335) or Short circuit (#336) of Compressor discharge gas sensor ( TDISR )
Countermeasure
<< Cause -(2) >>
Defective TDISR
< Check > ( Refer to Page F-28, CPE15-3BA3Y2 )
Remove the sensors from the terminal block TB11
and check the resistance between VRF and 61 ( TDISR ).
< Action >
• Approx. 600 kohm or over : Replace TDISR ( Disconnection ).
• Approx. 600 ohm or below : Replace TDISR ( Short circuit ).