Alarm Code #351
Model CPE52, 53, 14, 15, 15V, 16
Failure Current sensor (CT1) Low failure
Countermeasure
<<
Cause -(3) >> ( Refer to Page F-10, 19, 24
)
Relay
MC and CFR are not closed.
<
Check >
Operate
the compressor and the condenser fan under the test mode and check motion of
the relays.
<
Action >
• In
case the compressor does not operate :
Remove
the cause, such as High Pressure Switch ( HP ) actuation, etc.
• In
case the Condenser fan does not operate :
Remove the cause, such
as defective CFR relay, defective PCB-C board, etc.