Alarm Code #357
Model CPE52, 53, 14, 15, 15V, 16
Failure Current sensor for compressor ( CTM )
Low failure
Countermeasure
<<
Cause -(3) >>
CTM
sensor failure
<
Check > ( Refer to Page F-29 )
Perform
“ the compressor motor ON / OFF test ” under the test mode, and check the
following relation
between
the CTM sensor AC output voltage and the current value displayed on the
personal computer,
the LED
or the LCD of the current value indicated on a clamp meter.
< Relation between
the AC output voltage and the M2 current * >
(Note) Take an
interval of more than 5min at Compressor ON / OFF test.
< Action >
In case of No change in the voltage
with the compressor motor ON / OFF test : Replace CTM.