Alarm Code #422
Model CPE52, 53, 14, 15, 15V, 16
Failure Disconnection or Internal thermostat
actuation of Condenser fan motor
Countermeasure
<<
Cause -(2) >>
Defective
Condenser fan relay ( CFR )
<
Check > ( Refer to Page F-10, 25 )
Operate
the condenser fan motor under the test mode, and check the voltage on CFR relay
coil.
Check
also the coil current value on AC 24V circuit with a clamp meter.
<
Action >
• In
case the coil voltage is normal ( AC 24V ±10% ) and CFR does not work : Replace
CFR.
• In
case AC coil current is out of the following range : Replace CFR.
•
CPE52, 53, 15 : approx. 0.1 – 1A ( at AC 440V )
•
CPE14, 15V, 16 : approx. 0.1 – 2A ( at AC 440V )
• In case no coil
voltage is detected : Replace PCB-C board.