Mitsubishi Alarm Code #481 cause 1



Alarm Code #481
Model CPE52, 53, 14, 15, 15V, 16
Failure Short circuit of Evaporator coil heater Lo ( Sub-heater )
Countermeasure
<< Cause -(1) >>
Short circuit of all Evaporator coil Sub ( Lo ) heaters
< Check > ( Refer to Page 25 )
Supply electricity to all heaters under the test mode, and check the current with a clamp meter.
< Action >
In case the current is the following value at each Line*, replace Evaporator coil Sub heater ( Lo ).
• CPE52, 53 : approx. AC 5.5A or over ( at AC 440V )
• CPE14, 15, 15V, 16 : approx. AC 5.5A or over ( at AC 440V )
* HR2 : L1B (15A), L3B (20A)