Mitsubishi Alarm Code #356 cause 1



Alarm Code #356
Model CPE52, 53, 14, 15, 15V, 16
Failure Current sensor for compressor ( CTM ) High failure
Countermeasure
<< Cause -(1) >>
Main contactor MC continues to close with fused and stuck contact, etc.
< Check > ( Refer to Page F-12 )
Select “ Display test ” under the test mode to turn OFF all contactor relays, and check if the compressor is turned OFF.
< Action >
In case the compressor is not turned OFF : Remove the cause that the main contactor MC continues to close, or replace PCB-C board.