Alarm Code #356
Model CPE52, 53, 14, 15, 15V, 16
Failure Current sensor for compressor ( CTM )
High failure
Countermeasure
<<
Cause -(1) >>
Main
contactor MC continues to close with fused and stuck contact, etc.
<
Check > ( Refer to Page F-12 )
Select
“ Display test ” under the test mode to turn OFF all contactor relays, and
check if the compressor is turned OFF.
<
Action >
In
case the compressor is not turned OFF : Remove
the cause that the main contactor MC continues to close, or replace
PCB-C board.