P8 Tests - Perishable Mode Tests: Pretrip tests P7-0 and P7-1 must have passed or have been skipped for these tests to execute.
P8-2 Perishable Mode Maintain Temperature Test |
Test P8-1 must pass for P8-2 to execute. A fifteen minute timer is started, and the system will attempt to minimize control temperature error (supply temperature minus setpoint) until the timer expires. The control temperature will be sampled each minute starting at the beginning of P8-2. During P8-2, the left display will read “P8-2,” and the right display will show the supply air temperature. When the test is completed, the average control temperature error will be compared to the pass/fail criteria. Test passes if the average temperature error is within +/- 1.0 C. Test fails if the average temperature error is greater than +/- 1.0 C, or if the DataCORDER supply temperature probe is invalid. If the test fails, the control probe temperature will be recorded as -50.0 C. |