Trouble
shooting |
Possible causes:
- Hot gas valve not working probably.
- Defective Psuc.
- Defective Tevap.
Accompanied alarms:
- Maybe AL 207
- Maybe AL 12
- Maybe AL 610
Trouble shooting:
- If companied alarms AL 207 or AL 123 run troubleshooting for these alarms first.
- Hot gas valve is not working probably. Let the compressor run by 35 Hz in manual. Open hot gas valve 50% and control the valve function. Is the sound as usual? If not control with a permanent magnet and test coil function.
- If it looks like the hot gas valve is working as usual run function test step compressor. If alarms, look for troubleshooting for these alarms.
- If no alarms, run a manual activated defrost and follow the behavior of Tevap, Tsuc, Tret, and Psuc
|