844 StarCool Alarm Codes

844 Hot gas valve
Description Hot gas Valve Fault
Cause Indication of non-operating hot gas valve
Trouble
shooting
Possible causes:
• Cable for hot gas valve mounted on wrong valve.
• Cable for hot gas valve defective.
• Hot gas valve defective.
• Driver circuit for hot gas valve defective.
Trouble shooting:
1. Try to correct the error by uploading the latest software version to the
controller.
2. If there is more than one valve failure, the cables for the valves are
presumably switched.
Mount cables for valves on the correct valve.
3. Listen if the hot gas valve is opening and closing, if not go to step 5). If the
valve is opening and closing disconnect power to the solenoid coil, when the
valve is closed and there is hot temperature after the valve (pos. 32 in the
P – I diagram), the hot gas valve has a leak and should be replaced. Internal
parts of the hot gas valve can be replaced separately.
4. Check that the cable for the hot gas valve is not defective.
Replace cable if it is damaged.
5. Disconnect the cable for valve and measure that there is voltage on the
output for the hot gas valve when it should open.
a. If there is no voltage, the main controller is defective. Replace the main
controller.
Criteria
  • Pdis more than (>) 5 BarE: Max change on Pdis: ±0.75 Bar
  • Pdis is less than (<) 5 BarE: Max change on Pdis: ±0.30 Bar
  • Tret is more than or equal (≥) to -15°C: Min. change on T0: +20°K
  • Tret is less than (<) -15°C: Min. change on T0: +10°K