22 Capacity Test 1 Error (Check Alarm)

Thermo King Alarm Code
Description Corrective Action
Capacity Test 1 Error (Check Alarm)
  • Occurs during Pretrip (PTI) test only.
  • Difference between supply and return air temperature is too small with low speed evaporator fans (less than approximately 4.5C [8 F])
  • Return air temperature does not reach -18C (0 F) within preset time.
  • Indicates:
  • Incorrect location of supply or return air sensor
  • Air leakage at supply sensor cable
  • Defective supply or return air sensor
  • Interchanged sensor connections
  • incorrect evaporator fan rotation or high speed operation
  • Incorrect refrigeration system operation
  • Container/side panels defective, damaged or leaking
  • Enter Manual Function Test and start evaporator fans on LOW speed. Then select Sensor Checks test and operate fans 2 to 5 minutes. Check supply, return and evaporator coil (defrost) sensor temperatures. Sensor readings should be the same (evaporator coil may be 0.5 C [1.0 F] lower due to fan motor heat).
NOTE: This sensor check does not detect air leakage around the sensor cables.
  • Open evaporator door and inspect evaporator fan rotation. Make sure fans are rotating correctly on low speed.
  • Check the sensor connections.
  • Enter Manual Function Test menu. Start and check current draw of the following components separately and together: compressor, compressor 100%, condenser fan and evaporator fans (low). Check discharge and suction pressure readings. Also check the refrigerant charge.
NOTE: This alarm can be activated in ambient temperatures below -10 C (14 F), even under normal conditions.