Capacity Test 1 Error (Check Alarm)
- Occurs during Pretrip (PTI) test only.
- Difference between supply and return air temperature is too small with low speed evaporator fans (less than approximately 4.5C [8 F])
- Return air temperature does not reach -18C (0 F) within preset time.
- Indicates:
- Incorrect location of supply or return air sensor
- Air leakage at supply sensor cable
- Defective supply or return air sensor
- Interchanged sensor connections
- incorrect evaporator fan rotation or high speed operation
- Incorrect refrigeration system operation
- Container/side panels defective, damaged or leaking
|
- Enter Manual Function Test and start evaporator fans on LOW speed. Then select Sensor Checks test and operate fans 2 to 5 minutes. Check supply, return and evaporator coil (defrost) sensor temperatures. Sensor readings should be the same (evaporator coil may be 0.5 C [1.0 F] lower due to fan motor heat).
NOTE: This sensor check does not detect air leakage around the sensor cables.
- Open evaporator door and inspect evaporator fan rotation. Make sure fans are rotating correctly on low speed.
- Check the sensor connections.
- Enter Manual Function Test menu. Start and check current draw of the following components separately and together: compressor, compressor 100%, condenser fan and evaporator fans (low). Check discharge and suction pressure readings. Also check the refrigerant charge.
NOTE: This alarm can be activated in ambient temperatures below -10 C (14 F), even under normal conditions. |