High Pressure Cutout Switch Off Error (Check Alarm)
- Occurs during Pretrip (PTI) test only.
- Compressor does not stop during high pressure cutout switch test.
- Indicates:
- Faulty compressor contactor or control circuit
- Low refrigerant charge
- Defective high pressure cutout switch
- Strong winds causing cooling of condenser coil in low ambient conditions
|
- Enter Manual Function Test menu. Start the following components together: compressor 100%, compressor and evaporator fans (high). Discharge pressure should increase and compressor should stop (high pressure cutout switch opens).
- Check the refrigerant charge using the “Unit Health Check Procedure” on page 6-5.
|