52 Probe Error (Check Alarm)

Thermo King Alarm Code
Description Corrective Action
Probe Error (Check Alarm)
  • Occurs during Pretrip (PTI) test or Probe Test failed in Chilled mode.
  • Temperature difference between return air and evaporator coil sensors is too high (1.5 C [2.7 F] difference maximum)
  • Temperature difference between return air and supply air sensors is too high (0.8 C [1.5 F] difference maximum)
  • Temperature difference between LH supply and RH supply sensors is too high (0.5 C [1.0 F] difference maximum)
  • Indicates:
  • Incorrect temperature reading on one sensor
  • Supply air sensor not placed in airflow stream
  • Check sensor connections. Check sensor resistance of each sensor. Resistance must be 2,000 ohms at 25 C (77 F).
  • Check left hand and right hand supply air sensor locations.