11 Heater Current Too Low MP4000
Description
Heater Current Too Low
- Occurs during pretrip (PTI) or function test only.
- Heater power consumption is 25% below expected
current draw or phase current level differs 33% or
more.
- If both alarm #10 and #11 is active this indicates too
high phase difference.
- Expected heater current is a function of the heating
element resistance and the power supply voltage.
- The Magnum+ may be equipped with extended
heating capability.
- Normal heating element 4kw@460VAC
- - below approximately 3,7Amp / 3,2Amp.
- Extended heating element 6kw@460VAC
- - below approximately 5,6Amp / 4,8Amp.
- Indicates:
- Incorrect heaters or heater connections.
- Defective heating element.
- Defective volt or amp meter on power module.
Corrective Action
- Enter Manual Function Test and turn heaters
on. Check current draw on each phase.
Evaluate current draw in relation to expected
values.
- Enter configuration menu and check the
heating element setting.
- Check heater resistance.
- The electrical resistance towards chassis must
be above meg ohm (MΩ) range.
- Normal heating element 4kw@460VAC
- - expects 5,0Amp@460VAC
- - expects 4,3Amp@400VAC
- - expected resistance 99Ω on each leg.
- Extended heating element 6kw@460VAC
- - expects 7,5Amp@460VAC
- - expects 6,5Amp@400VAC
- - expected resistance 66Ω on each leg.
6 comments :
Your blog is very interesting.Thanks for sharing this with us and keep sharing these types of blogs.
UI UX
This is very informative blog for everyone.Thanks for sharing this article with us.
Cyber security
Very well describe information!Thank you for sharing this with us.
salesforce solution
Great blog! nice work.You have good experience of working.
BI tools
Your blog is very nice.I really appreciate your work.Thanks for sharing this with us.
data management
hi
Post a Comment